Application:
The instrument is used for the program control in single stage of RO produce water systems, and also the conductivity measurement and control.
Features:
LED display, perfect performance
With typical reverse osmosis operation program inside, users only need to set parameters
Automatic measure range, digital temperature compensation
low pressure pull-up voltage, photoelectronic seclusion input
Dry contact is used on all control terminals
Calibration of electrode constant, conductivity alarm setting
AC 220V power supply.
Model: CCT-7320/9320
Reverse osmosis collection point:
raw water no water protection, low pressure protection, high pressure protection, pure water tank high level protection, exterior operation, reset.
Reverse osmosis control point:
raw water pump, high pressure pump, inlet water valve, flush valve, conductivity over limit discharge valve
Measurement item: conductivity/temperature
Auxiliary electrode: two-electrode type
Display mode: 3 1/2 digits red LED digital display
Auxiliary electrode: 1.0cm-1 electrode
Measurement range:
Conductivity 0.0μS/cm~200.0 μS/cm
Temperature 0~50℃
Resolution ratio:
Conductivity 0.1μS/cm
Temperature 0.1℃
Accuracy: Conductivity ≤1.5%
Temperature ≤0.5℃
Temperature compensation:
automatic digital compensation with 25℃ as reference temperature
Environment condition: temperature: 0-50℃ humidity : ≤85%RH
Electrical control:
ON single contact relay, dry contact (no power) output
Contact capacity: AC 230V/5A Max;AC 115V/10A Max(Resistance load)
Power supply: AC 165V~260V 50Hz
Outline dimension:
ROC-2313 96 mm×96 mm×130mm(H×W×D)
ROC-3313 130 mm×180 mm×60mm(H×W×D)
Hole size: ROC-2313 91 mm×91mm(H×W)
ROC-3313 122 mm×172mm(H×W)
Installation: panel mounted
|
??????? ???????? ?????? ?????
????? ?????? 03-6764586